• The FBCW silicone-insulated parallel resistance heat trace cable is designed for industrial applications. Its uses include:
• Freeze protection or temperature maintenance of vessels and tanks.
• Freeze protection for chemical feeding or process lines.
• This cable ensures safe and effective heat tracing in various industrial environments.
• Suitable for use in hazardous and non-hazardous locations.
Max. maintain temperature (Power-on) 100°C (212°F)
Max. withstand temperature (Power-off) 150°C (302°F)
Rated voltage : 100 ~ 120 Vac, 200 ~ 240 Vac
Rated power output : 10, 20, 30, 40 watt/m@20°C
Max. circuit length : 100m
Node interval :
10, 20 w/m model : 100cm
30, 40 w/m model : 50cm
Conductor size :
10 w/m model : 0.75mm?
20, 30, 40 w/m model : 1.25 mm?
Cable dimension (nom.) :
10 w/m model : 9.5mm x 7.5mm
20, 30, 40 w/m model : 11.5mm x 8.0mm
Outer jacket (Optional) :
CS : Silicone rubber
CT : Fluoropolymer