LBSC-7000 sensing cable is designed for various applications :
semi-conductor factory
battery factory
display panel (LCD/LED) factory
all other chemical plants
Applicable chemical : sulphuric acid,
hydrochloric acid, nitric acid,
and PAC etc.
- Conforms with EMI/EMC and
Electrical Safety requirements
- Sensing cables can be extended up to 1km
- Fast response 8 seconds max. depending on liquid type
- Leak positioning accuracy (± 1m /1,000m)
- Resistance to abrasion, chemicals
- Standard supply 3.5m, 7m, 15m
- Operating temp. -40°C ~ 80°C
Cable diameter approx. 7 mm
Continuity wire AWG 20 x 2
Sensing wire:
Spacer chemical resistant XLEVA, grey color
Maximum continuous operating temperature 80°C
Humidity up to 80% RH
Flame retardant VW-1
Min. bending radius 40mm
Min. installation Temperature -40°C
Pre-terminated standard length 3.5m, 7m or 15m
CPC connector polyester/glass-filled nylon Max. Ø25mm