PYEX-EP-JBS

PYEX-EP-JBS

PYEX-EP-JBS

PYEX-EP-JBS Exproof GRP Junction Box

The PYEX-EP-JBS is an Ex certified GRP enclosure system being designed and manufactured to meet all requirements from relevant international standards for industrial heat 
tracing cable system especially for hazardous location such as petrochemical plant, gas  plant, ship and off-shore plants etc. 

Protection Type : Ex eb IIC
Applicable heating cables in hazardous location : FBL, FBH, FBX, FBZ
Temperature classification
FBL : T6 (85℃)
FBH : T4 (135℃)
FBX15x / 30x / 45x, FBZ15x / 30x / 45x : T3 (200℃)
FBX60x, FBZ60x : T2 (220℃)
Enclosure service temperature : -55℃ to 135℃
Stainless steel pipe-mount service temperature on the pipe : -50℃ to 300℃
Max rated voltage 277Vac
Max load current : 30A for PYEX-EP-JBS-12, 16 & 26
Ingress Protec

Protection Type : Ex eb IIC
Applicable heat trace cables in hazardous location : FBL, FBH, FBX, FBZ
Temperature classification
FBL : T6 (85℃)
FBH : T4 (135℃)
FBX152 / 302 / 452, FBZ152 / 302 / 452 : T3 (200℃)
FBX602, FBZ602 : T2 (300℃)
Enclosure service temperature : -55℃ to 135℃
Plastic heating cable gland (PYEX-EP-PG25) service temperature : -40℃ to 110℃
Max rated voltage 277Vac
Max load current : 50A for PYEX-EP-JB-12 & 16, 100A for PYEX-EP-JB-26
Ingress Protection : IP65 (when assembled with heating cables)
Enclosure Material : Glassfibre reinforced polyester / UV stabilized
Impact Resistance : 7J
Flammability : Self-extinguishing UL 94/V-0
Color : Graphite Black
Gasket and Seal : Flame-proof silicone rubber
Maximum power conductor cross-section : 10mm⊃2;
Thread for power cable entry : Max. M25, PF3/4, NPT3/4-14
Approval : ATEX, IECEx
Reference standards : IEC60079-0, IEC60079-7, IEC